4 · Flow temperature
What heat output suits your heating system?
The output shown in the shop is for 75/65/20 °C according to EN 442. If your heating system runs cooler, for example with a heat pump, the same radiator will output less heat. Enter the output from the product page.
Specify the power at 75/65/20 °C.
How it is calculated
Output = output at 75/65/20 °C × (ΔT ÷ 49.83 K)n, using the logarithmic excess temperature ΔT = (flow − return) ÷ ln((flow − room) ÷ (return − room)) according to EN 442. We use the exponent n from the datasheet; if none is specified, we use the standard value 1.3.