Underfloor heating isn't getting warm: Narrow down the causes

If a room remains cold, the cause could be the manifold, actuator, air, or the heating setting. Here’s how to narrow down the cause step by step.

by Helia Bad Redaktion6 min read

Natursteinboden im Morgenlicht mit Hausschuhen und Bademantel auf einem Hocker – wenn die Fußbodenheizung nicht warm wird

In short: If the underfloor heating doesn't get warm, the cause is usually one of four things: the heating setting, the manifold with its actuators, air in the heating circuit, or expectations. After all, underfloor heating only feels slightly warm and reacts slowly. A few simple steps will help you narrow down the cause.

By late November, the heating season is in full swing, and this is the latest you'll notice if a room isn't getting warm enough. The tiles in the bathroom remain cool, while the hallway is cozy. Or the entire ground floor doesn't get properly warm, even though the heating is on.

Underfloor heating is a silent system. You can't see it, you can hardly hear it, and that's why a fault often seems baffling. With a clear procedure, however, you can usually find the cause quickly, or at least know what to tell the heating specialist.

First check: Is it really too cold?

Underfloor heating operates at low temperatures. The floor only feels slightly warm, not hot like a radiator. The DIN EN 1264 standard limits the temperature at the floor surface to ensure that walking on it remains comfortable. In a well-insulated house, the floor is often barely warmer than the room air, and the room still gets warm.

The room temperature is therefore what matters, not the feeling underfoot. Measure it with a thermometer at sitting height. If the room reaches its desired temperature, the underfloor heating is probably working correctly.

Also keep inertia in mind. After a long break, such as over the summer, the screed can take many hours to heat up completely. If you turn it on in the morning and the tiles are still cold at noon, you may only be seeing this delay.

Underfloor heating doesn't get warm: narrow down the causes

Whether one room or the entire house is affected already tells you a lot. The overview below helps you identify the cause:

What you notice Possible cause What to check
all rooms too cool heating in summer mode, heating curve too low mode of operation and heating setting
all rooms too cool, radiators warm underfloor heating mixer or pump temperature at the manifold
one room cold room thermostat or actuator batteries, setting, actuator
one room cold, zero flow valve at the manifold is stuck valve pin at the manifold
gurgling, individual circuits cold air in the heating circuit bleed and flush

Check the manifold

The heating circuit manifold is the heart of the underfloor heating system. This is where the heating water arrives and is distributed to the individual heating circuits. The flow meters are often located on the flow pipe, while the actuators, which open or close each circuit, are on the return pipe.

Follow these steps:

  1. Check whether the manifold is warm. If the flow pipe is cold, the cause is before the manifold, i.e., the heating, mixer, or pump.
  2. Read the flow rate of the cold circuit. If it shows nothing, the circuit is closed or blocked.
  3. Examine the actuator for this circuit. Many have an indicator showing whether they are open.
  4. Check the room thermostat: Is it set high enough? Are the batteries charged?
  5. Carefully remove the actuator. On many models, this opens the valve completely. If the room gets warm afterwards, the problem is the actuator or room thermostat.

If the valve remains closed even without the actuator, its pin is probably stuck, similar to a radiator valve after summer. Our article Stuck valve pin explains what this looks like and how to carefully help. The same applies to the manifold: move it, but do not unscrew the valve body.

Important: Do not change the settings of the flow meters without making a note of them. They were set during the hydraulic balancing. Photograph the manifold beforehand. Work on the mixer, pump, pressure, and connections, as well as connecting actuators to the control system, should be carried out by a heating specialist.

Air and sludge in the heating circuit

In underfloor heating, air tends to collect in individual circuits. Typical signs are gurgling at the manifold and circuits that remain cold even though everything is open. Bleeding alone is often not enough here because the air is trapped in the long pipe loops. In that case, the circuit must be flushed.

Older underfloor heating systems sometimes have a different problem: sludge. This is caused by oxygen entering the heating water over many years and causing steel components in the system to rust. The sludge settles in the pipes and at the manifold and slows the flow. Read Bleeding and flushing underfloor heating to find out when bleeding and flushing are necessary.

If the underfloor heating is being replaced or expanded, you can prevent sludge by using oxygen-barrier pipes. Our PE-RT 16 × 2 mm underfloor heating pipe has a 5-layer construction with an oxygen barrier. You can find all pipes under PE-RT pipes.

If everything is correct and it still remains cool

Sometimes everything is technically in order, yet the room still remains cool. In that case, take a look at the room itself:

  • Thick rugs or furniture without feet cover a large part of the floor area.
  • New flooring provides more insulation than the old flooring.
  • The room requires more heat than the underfloor heating can provide at the selected temperature.
  • In the bathroom, the bath, shower, and furniture stand on part of the floor area, reducing the heated area.

In such cases, a supplement, such as a bathroom radiator, or a new setting by a specialist may help.

Frequently asked questions

How warm should underfloor heating feel?

Only slightly warm, significantly cooler than a radiator. The floor temperature is limited to ensure that walking on it remains comfortable. A good measure is the room temperature, not the feeling underfoot.

Can I adjust the flow meters on the manifold?

It is better not to do so without a good reason. They were set during the hydraulic balancing to ensure that each room receives the right amount of heat. If you make any changes, note the setting beforehand or have a specialist do it.

How long does it take for underfloor heating to get warm?

Depending on the screed and insulation, it can take hours rather than minutes. After a long break, it takes even longer. That is why it is usually operated continuously rather than being switched on and off frequently.

Can I remove an actuator myself to test it?

Many actuators can be removed and reattached without tools. However, the electrical connection to the control system should be carried out by a specialist.

Expanding or replacing underfloor heating?

Write to us with the pipe dimensions of your system and what you plan to do. We will help you with the specifications for our PE-RT pipe.

Send us a question View PE-RT pipes

More on this topic:Maintenance

Radiator Finder

Find the right radiator in three questions

Question 1 of 3

How should the radiator be heated?
Replace an old radiatoropen the replacement finder (centre distance)

View calculation or consider flow temperature? Calculate the heating load for your room

More from the shop

Browse all models, sizes and colours.

View PE-RT pipes